name

York 025-29139-003 Pressure Transducer
YORK

Description

York 025-29139-003 is a genuine high-precision pressure transducer for industrial HVAC, centrifugal/screw chillers, refrigeration systems. Measures 0-275 psi (0-18.96 bar), 4.75-5.25 VDC input, 0.5-4.5 VDC ratiometric output. 1/4"-18 UNF port, stainless steel construction, fast response, high stability. Ideal for refrigerant, oil, water pressure monitoring in YORK YK/YT chillers, ensuring accurate data feedback and safe system operation.

Product Details

The Johnson Controls 025-29139-003 (YORK OEM) pressure transducer is a high-performance, piezoresistive pressure sensor engineered for precise pressure monitoring in industrial refrigeration, commercial HVAC, water-cooled chillers, and screw/centrifugal compressor systems. As a genuine YORK replacement part (P/N: 025-29139-003), it is purpose-built for YORK YK, YT, and similar chiller models to deliver reliable pressure measurement of refrigerants, lubricating oil, and water circuits.

This transducer operates on a 4.75–5.25 VDC power supply and provides a proportional analog output of 0.5–4.5 VDC, ensuring seamless compatibility with chiller control panels and building management systems (BMS). It features a measurement range of 0–275 psi (0–18.96 bar), high accuracy, minimal thermal drift, and rapid response time for real-time pressure feedback.

Constructed with a stainless steel pressure port and robust housing, it withstands vibration, temperature fluctuations, and harsh industrial conditions. The standard 1/4"-18 UNF threaded connection simplifies installation and replacement. With high stability, long service life, and anti-interference performance, this transducer ensures accurate pressure regulation, overload protection, and safe, efficient operation of chiller and refrigeration systems.

ParameterSpecification
Model Number025-29139-003 (YORK OEM)
BrandJohnson Controls (York)
Product TypePressure Transducer / Pressure Sensor
Pressure Range0 ~ 275 PSI (0 ~ 18.96 bar)
Power Supply4.75 ~ 5.25 VDC (Class 2)
Output Signal0.5 ~ 4.5 VDC (Ratiometric)
Sensing TechnologyPiezoresistive
Process Connection1/4"-18 UNF Thread
Wetted MaterialStainless Steel
Accuracy±0.5% FS (Typical)
Response Time< 1 ms
Operating Temperature-40°C ~ +125°C (-40°F ~ +257°F)
Proof Pressure400 PSI (27.58 bar)
Burst Pressure1000 PSI (68.95 bar)
ApplicationYORK YK/YT Chillers, HVAC, Refrigeration, Oil/Water Systems
OriginChina (OEM for YORK)

More Products

York 025-28678-006 Pressure Transducer

York 025-28678-006 Pressure Transducer

YORK
York 025-29139-001/S1-025-29139-001 Pressure Transducer

York 025-29139-001/S1-025-29139-001 Pressure Transducer

YORK
York SC0517 025-43553-000 Water Flow Switch

York SC0517 025-43553-000 Water Flow Switch

YORK
York 031-01267-001A Replacement Furnace Control Board

York 031-01267-001A Replacement Furnace Control Board

YORK